Sr. No. | Properties | Cross linked | Thermoplastic (Other Products) |
1 | Thermal Resistance | Max. operating temperature 90°C | Max. operating temperature 70°C |
2 | No change under heat | Deform and soften under heat | |
3 | Max. short circuit temp. rating 250 °C | Max. short circuit temp. rating 160 °C | |
4 | Structure | 3-Dimensional structure | Usually linear in structure |
5 | Hygroscopic nature (Higher water absorption reduces electrical properties) | Non Hygroscopic | Comparatively hygroscopic |
6 | Electrical Properties | Higher dielectric strength | Lower dielectric strength |
7 | Higher current carrying capacity | Lower current carrying capacity |
Test | Test Method | Values |
Limited Oxygen Index | ASTM-D 2863 | 34% |
Limited Temperature Index | ASTM-D 2863 | > 350°C |
Smoke Density (Light Absorption) | ASTM-D 2843 | < 7% |
Acid Gas Generation | IEC-60754-1 | 0.0% |
Nominal cross sectional area of conductor | Number/Nominal dia of strands | Nominal insulation thickness | Max. Overall diameter | Max conductor resistance at 20°C | Current rating | |
Casing | Concealed | |||||
Sq.mm | mm | mm | mm | 0/km | Amps | Amps |
1 | 14 / 0.30* | 0.7 | 3.2 | 18.1 | 14 | 13 |
1.5 | 22 / 0.30* | 0.7 | 3.4 | 12.1 | 18 | 16 |
2.5 | 36 / 0.30* | 0.8 | 4.2 | 7.41 | 24 | 20 |
4 | 56 / 0.30** | 0.8 | 4.8 | 4.95 | 32 | 26 |
6 | 84/0.30** | 0.8 | 6.4 | 3.30 | 36 | 32 |
Extreme temperature range: | (-40oC to 105oC) can withstand the extremes of automotive environments |
ZHFR Cable range: | OGA, 2GA, 4GA, 6GA, 8GA, 10GA, 12GA, 14GA, 15GA, 16GA, 18GA, 20GA and ultra classic strands |
High strand counts | High strand counts |
Conductor Type | Stranded 99.99% OFC (oxygen free copper), and tin plated copper,copper coated al |
Material | Environmentally friendly, quality, glossy material Tinned, Silver or Nickel plated copper etc. |
ZHFR Cable Colour | Customized |
Packing | carton packing, pallet packing , wooden / plastic reels |
FLEXIBLE (Temperature upto 90 C) (Zero Halogen Flame Retardant Thermo Plastic) | |||||
Nominal crosssectional area of conductor | Nos & Diameter of Wires | Nominal thickness of insulation | Approx. Overall Diameter of Wire | Current rating 2 cable single phase ac/dc | Max DC Resistance at 20 Deg. C |
sq. mm | mm | mm | mm | Amps | ohm/km |
1 | 14/0.3 | 0.7 | 2.8 | 13 | 18.1 |
1.5 | 22/0.3 | 0.7 | 3.1 | 16 | 12.1 |
2.5 | 36/0.3 | 0.8 | 3.8 | 22 | 7.41 |
4 | 56/0.3 | 0.8 | 4.4 | 30 | 4.61 |
6 | 84/0.3 | 0.8 | 5.1 | 38 | 3.08 |
10 | 140/0.3 | 1 | 6 | 51 | 1.91 |
FLEXIBLE (Temperature upto 125 C) (Zero Halogen Flame Retardant Thermo Setting) | |||||
sq. mm | mm | mm | mm | Amps | ohm/km |
1 | 14/0.3 | 0.7 | 2.8 | 13 | 18.1 |
1.5 | 22/0.3 | 0.7 | 3.1 | 16 | 12.1 |
2.5 | 36/0.3 | 0.8 | 3.8 | 22 | 7.41 |
4 | 56/0.3 | 0.8 | 4.4 | 30 | 4.61 |
6 | 84/0.3 | 0.8 | 5.1 | 38 | 3.08 |
10 | 140/0.3 | 1 | 6 | 51 | 1.91 |
A brief comparison of PVC and ZHFR Cables is given below. | ||
Properties | PVC | ZHFR |
Halogen Gas (mg/g) | >200 | <0.5 |
Corrosive gas (pH) | 1-2 | 6 |
Smoke Density (Rating) | >70 | <20 |
0 Usage Temperature ( C) | 70 | 90 |
0 Low Temperature ( C) | -20 | -50 |
Dioxin | YES | NO |
Toxic Halogen Gas | YES | NO |
Lead | YES | NO |